Registered Address: 32D Floor Guomao Building, No.388, Hubin South Road, Siming District, Xiamen,Fujian, China
ABB CI860, article number 3BSE032444R1, is a communication interface that connects FOUNDATION Fieldbus High Speed Ethernet devices to AC 800M. Together with the TP860 baseplate, it provides one RJ45 connection for standard 10Base-T or 100Base-TX cabling at 10 or 100 Mbit/s.
CI860, article number 3BSE032444R1, connects FF HSE devices to AC 800M and can reach H1 devices through a compatible linking device. Match the TP860, processor type and stored configuration before commissioning.
Important Notice: Confirm the complete model, revision and installed system before replacement.
Connect the FF HSE network to the RJ45 port on TP860 using the documented 10Base-T or 100Base-TX Ethernet arrangement. Verify switch configuration, addressing, linking devices and the engineered HSE subnet before downloading the controller project.
When H1 devices are required, use a compatible HSE linking device such as LD 800HSE. Configure H1 links and assign the actual devices in ABB Fieldbus Builder before loading the CI860 configuration.
CI860 supports redundant operation and indicates primary and dual mode from the front LEDs. The two interfaces, TP860 baseplates, CEX-Bus positions and network paths must match the approved AC 800M redundancy design.
Use the Control Builder Switch Primary function only with a supported system version. Confirm traffic and run status on both interfaces before placing the redundant pair into process service.
Install CI860 on the correctly coded TP860 and confirm that the AC 800M processor is not a High Integrity model. Verify CEX-Bus power, RJ45 link status, addressing and the stored configuration before project download.
Fieldbus Builder FF and Control Builder load the CI860 settings with the controller application. Validate HSE and any linked H1 live lists, device assignment and primary/dual status after commissioning.
Engineering check: Seat CI860 on the TP860 and verify the RJ45 port, 10/100Base-TX switch configuration, IP addressing and controller project all reference the same FF HSE interface.
Acceptance test: Confirm scheduled and unscheduled HSE traffic reaches the intended fieldbus linking devices, then interrupt and restore the Ethernet path while checking stale-data handling, interface diagnostics and automatic reconnection.
ABB continues to document CI860 in current AC 800M hardware and Compact Control Builder releases, including support for primary switching in redundant configurations. The package remains tied to TP860 and is not approved for AC 800M High Integrity controllers.
Moore Automated supplies high-quality ABB CI860 communication-interface modules and related spare parts matched to 3BSE032444R1 or CI860K01. Exact package and controller checks help provide a reliable replacement solution and reduce FOUNDATION Fieldbus service downtime.