Registered Address: 32D Floor Guomao Building, No.388, Hubin South Road, Siming District, Xiamen,Fujian, China
ABB AI630 is an S600 I/O analog input module designed for twelve Pt100 resistance-temperature inputs. The module converts the connected sensor signals for use by the associated control system and must be matched to the installed S600 I/O station, termination arrangement and channel configuration. Article identity and field wiring should be verified before replacement.
Every sensor circuit and input assignment should be checked against the installed system before replacement.
Important Notice: Confirm the complete model, revision and installed system before replacement.
AI630 provides twelve documented Pt100 analog inputs. Verify the field-wire arrangement against the applicable ABB station and termination documentation.
Match the installed station, controller interface, termination hardware and channel map before inserting the replacement module.
Check sensor continuity, lead compensation, channel assignment and engineering values before returning each temperature loop to service.
Engineering check: For AI630, identify every Pt100 circuit and confirm the documented lead-wire arrangement, terminal assignment and shield practice. Measure loop resistance before connection and isolate open, shorted or grounded sensor wiring.
Acceptance test: Inject traceable resistance values into all 12 channels and verify displayed temperature, channel order, engineering-unit scaling and configured open-circuit or out-of-range alarms across the S600 station.
Moore Automated supplies high-quality ABB AI630 replacement modules and S600 I/O spares. Article, station, termination and channel wiring are verified before supply to reduce commissioning risk and process downtime.