TA25DU-1.8M is an ABB thermal overload relay used with the documented Safety Automation platform. Selection must match the complete product identity, hardware execution, connected assemblies and approved system configuration.
Before replacing TA25DU-1.8M, compare the supplied nameplate, revision, connectors or terminals and installed position with the original equipment record. After installation, review diagnostics and complete the approved functional checks before service.
ABB TA25DU-1.8M documentation and reference links.
Important Notice: Every linked document must identify the listed model or its documented family. Confirm the complete order code, hardware revision and installed-system requirements before replacement.
This execution covers 1.30-1.80 A. Set the front dial to the motor and approved starter design, retaining the documented setting during replacement. The upper value in the model name is not an instruction to set every motor to 1.8 A. Starting duration and loading must also suit the class 10A characteristic.
ABB's catalogue row for 1SAZ211201R2025 lists 6 A gG or 4 A aM fuse coordination. These values are linked to the published starter and short-circuit conditions; they are not universal circuit-breaker substitutes. Confirm the receiving contactor, prospective fault level and protective-device arrangement before applying the combination.
Contact 95-96 is the normally closed trip path; 97-98 is a separate normally open indication path. Restore their original circuit assignments and check the TEST and STOP functions with the starter isolated and controlled by qualified personnel. Automatic reset must not cause an unintended motor restart.
For a replacement, match TA25DU-1.8M and ABB order code 1SAZ211201R2025, then record the existing ampere setting, reset mode and contactor reference. The 1.30-1.80 A band must cover the required motor setting; a similar TA25DU housing with another suffix is not an equivalent current range. Include the wiring identification for contacts 95-96 and 97-98 and any separately fitted mounting accessory.
Provide the quantity, motor full-load current, starting duty, installed contactor and short-circuit protective device. State whether the order requires the relay only or includes a separate mounting kit, together with the receiving country and required delivery date. Moore Automated will identify the exact current-band execution and included accessories in the quotation; suitability of the complete starter remains subject to the approved circuit design.