Allen-Bradley 1440-VAD02-01RA is the XM-123 Aeroderivative vibration monitoring module. It provides two configurable dynamic measurement channels, one tachometer input, two isolated 4-20 mA outputs, one onboard double-pole relay and DeviceNet communication for documented aeroderivative gas-turbine monitoring systems.
1440-VAD02-01RA is the exact XM-123 aeroderivative execution and is not interchangeable by appearance with another XM dynamic module. The terminal base, transducer type, channel configuration, firmware, DeviceNet node and protection logic must match the controlled installation.
Before removal, record the complete label and series, 1440-TB-A wiring, channel transducers, tachometer source, filters, alarm setpoints, relay logic, 4-20 mA scaling, DeviceNet address and current configuration backup. After installation, validate every measurement and protection path.
XM-123 provides two dynamic measurement channels, one tachometer input, two isolated 4–20 mA outputs and one double-pole relay.
The module uses the 1440-TB-A XM-940 terminal base and the documented DeviceNet node settings. Preserve the approved firmware and configuration.
Check sensor bias or power, speed input, analog-output scaling, relay action and every affected alarm or shutdown path.
Archive each channel mode, transducer selection, engineering units, sensitivity, filter bandwidth, FMAX and tachometer pulses-per-revolution setting. Restore only the approved measurement configuration.
Record alarm thresholds, delays, latching or failsafe behavior and the assigned analog-output and relay logic. Validate the saved configuration against the controlled machinery-protection cause-and-effect record.
Obsolete / Discontinued by OEM
Allen-Bradley 1440-VAD02-01RA is the XM-123 Aeroderivative vibration monitoring module. It provides two configurable dynamic measurement channels, one tachometer input, two isolated 4-20 mA outputs, one onboard double-pole relay and DeviceNet communication for documented aeroderivative gas-turbine monitoring systems. Moore Automated confirms the offered unit's exact marking, condition, availability, included accessories and supply scope in the written quotation.