Honeywell's IO03-684 identifies MC-GHAO11 as the coated, GI/IS 16-output analog-output FTA with a HART connector and no standby-manual connectors, for use only with MU-PAOY22. The document lists MC-GHAO11 as a model but does not map numeric order suffix 51309540-175 to it separately; verify the full supplied marking and system configuration.
Honeywell's TPS Process Manager I/O specification (IO03-684, December 2012, Revision 2) lists MC-GHAO11 as the coated GI/IS analog-output FTA for 16 outputs, without standby-manual connectors and with a HART connector. The model table states that it is used only with MU-PAOY22 and that the MC models are conformally coated. The associated GHAO11 family specification is 4-20 mA with 16 channels. The document does not separately associate listing suffix 51309540-175 with this model, so that numeric mapping must be confirmed from the supplied item label.
Before installation, verify the complete FTA and IOP labels, approved I/O drawings, field-device and intrinsic-safety loop design, HART connector arrangement, redundancy use, and terminal/wiring details. Compare the loop burden with the GHAO11 family values under the stated supply condition; do not generalize ratings from the other 16-point FTA models in the same table. Follow the applicable Honeywell installation and safety instructions, and test each affected channel and alarm or failover behavior under the site's approved commissioning procedure before process release.
Honeywell lists MC-GHAO11 as the coated GI/IS analog-output FTA with a HART connector, without standby-manual connectors, for use only with MU-PAOY22. Confirm the exact FTA and IOP labels, connector style, coating and approved configuration. The model row does not independently map numeric order suffix 51309540-175 to MC-GHAO11.
The GHAO11 family table states 16 channels of 4-20 mA, an 870-ohm maximum resistive load at 20 mA and 17.4 V maximum compliant output under the stated 24 V supply = 20 V condition. It lists +/-0.45% calibrated accuracy at 25 C including linearity for MU-GHAO11. Apply these family figures only after confirming the exact matched IOP, supply and loop conditions; do not borrow limits from the other FTA models.
Honeywell's redundancy-option table lists a 20 ms maximum output gap on failover and switching-hardware diagnostics once per minute. The catalog marks the FTA for single or redundant applications, but the installed IOP, wiring and logic determine the actual arrangement. Confirm the intrinsic-safety design and approved process state, and test channels and failover under site procedures before return to service.
Confirm MU-PAOY22 is the connected processor and check each loop against the GHAO11 family limit of 870 ohms at 20 mA and 17.4 V maximum compliance under the specified 24 V supply = 20 V condition. Verify field-device demand, wiring resistance, barriers/isolators and supply conditions together; the table's other FTA model values differ. Record the channel assignments and test output scaling and HART-related connections using the approved commissioning procedure.
The source identifies the FTA as GI/IS, usable in single or redundant applications, and says the model has no standby-manual connectors. The separate redundancy table gives a maximum 20 ms output gap on failover for the named family. Confirm the site's approved intrinsic-safety entity/loop documentation, IOP redundancy hardware, channel configuration and safe-state behavior. Only qualified personnel should make changes; inspect the actual terminal/field barriers and verify channel and failover operation before process return.