Registered Address: 32D Floor Guomao Building, No.388, Hubin South Road, Siming District, Xiamen,Fujian, China
The 3500/33 149986-01 is the front control module for a 16-channel relay assembly. It applies configured alarm-drive logic to the selected relay output module. Each channel can use individual or combined monitor conditions from the 3500 rack.
Program each channel from the required rack alarm conditions. AND/OR logic can combine measured-variable, Alert, Danger and Not-OK states rather than relying on one fixed alarm source.
Choose the 149992-series rear output module to suit standard, failsafe or low-current duty. Contact ratings and minimum switched load depend on that selection and the installation approval.
Standard, hazardous-area and functional-safety systems do not share every contact-voltage allowance. Use the relevant manufacturer rating table and disconnect power before service.
Identify 149986-01 on the front control module and photograph the separate 149992-series output-module label. Record the standard, failsafe or low-current variant, any revision marking and the installed configuration reference. A front-panel photograph alone does not identify the relay-contact option.
Provide quantity, full 3500/33 149986-01 identification, front/rear label photographs and the rack configuration reference. State whether the output module is included in the request and identify its exact part number; add the receiving country and required delivery date.