Honeywell 2104B2111 RX SHORT is a Searchline Excel short-range ATEX receiver for an open-path infrared flammable-gas detection system. The official product guide identifies a 5 to 40 m short-range optical path. Confirm the complete receiver code, matching transmitter, hazardous-area approval, mounting and alignment data before replacement.
2104B2111 is the receiving element of a paired Searchline Excel open-path infrared flammable-gas detector. It measures the infrared signal transmitted across the protected path and provides the system output used by the receiving controller. The installed transmitter, path length, gas calibration, source-loop wiring and hazardous-area certification must remain compatible.
Before removal, record the complete label, certification, paired transmitter, bracket position, path length, cable entries, terminal wiring, loop polarity, alignment readings and alarm configuration. After installation, align the optical path, verify stable signal strength, prove output and fault states, then perform the approved gas-response and alarm test.
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
The 2104B2111 receiver belongs to the short-range Searchline Excel execution with a documented optical path of 5 to 40 m. The paired transmitter and receiver must be mounted on the approved brackets with a clear line of sight and the alignment maintained within the system limits.
Record the existing bracket position and alignment readings before removal. After replacement, complete coarse and fine alignment and verify stable signal strength before performing gas-response tests.
The receiver is used with a source 4 to 20 mA output execution and the Searchline Excel system supports RS-485 Modbus communications. Confirm loop polarity, maximum loop resistance, receiving-channel scaling, fault-current behavior and any serial settings from the installed design.
Do not commission the channel from a normal current reading alone. Prove normal, fault and gas-response states at the controller and verify the configured alarm and shutdown actions.
Confirm hazardous-area isolation, cable-entry sealing, earth bonding, bracket condition and optical-window cleanliness before installation. Match the exact ATEX receiver execution and use the approved alignment procedure with the correct short-range transmitter.
After alignment, allow the detector to stabilize, record signal strength and prove the complete detection loop using the approved Searchline Excel test equipment and site gas-detection procedure.
Verify the paired short-range transmitter, 5 to 40 m path and approved mounting arrangement. Preserve bracket references and alignment records before removal. After installation, clean the optical windows, complete coarse and fine alignment, then confirm stable signal strength across the full protected path.
Verify the 18 to 32 VDC supply, 4 to 20 mA source-loop polarity, receiving-channel scaling and documented fault currents. Complete optical alignment first, then prove normal, fault and gas-response outputs, controller alarms and shutdown actions using the approved site test procedure.
Obsolete / Discontinued by OEM
Moore Automated supplies 2104B2111 RX SHORT after confirming the exact model, supplied condition and required system compatibility. Every unit is inspected before shipment to support stable operation and reduce unplanned equipment downtime.