Registered Address: 32D Floor Guomao Building, No.388, Hubin South Road, Siming District, Xiamen,Fujian, China
Woodward 5466-1035 is a CPU5200 processor module for a compatible MicroNet Plus control system. The documented module uses a PowerPC 5200 processor, 400 MHz clock, 64 MB flash, 128 MB RAM and dual CAN interfaces. Woodward marks it non-preferred for new installations and gives a planned 2028 inactivation date subject to change; verify coder/firmware, RTN pairing and application backup before replacement.
Woodward 5466-1035 is a MicroNet Plus CPU5200 module used in a compatible turbine-control platform. The manufacturer documentation identifies the CPU5200 architecture and relevant coder compatibility range; module substitution depends on installed software and system configuration.
Before replacement, record the complete part and revision, MicroNet Plus chassis, control application, coder/firmware footprint, RTN module pairing, tunables and communication setup. Preserve application and tunable backups and confirm support status with Woodward before making a migration decision.
Match the CPU5200 module, MicroNet Plus chassis, coder range and installed firmware footprint.
Back up the GAP application, tunables, configuration and communication settings before CPU replacement.
Woodward identifies 5466-1035 as non-preferred and publishes a planned 2028 inactivation; future dates are not guaranteed.
Woodward identifies 5466-1035 as a MicroNet CPU5200 module for MicroNet Plus, with a PowerPC 5200 processor at 400 MHz, 64 MB flash, 128 MB RAM and dual CAN interfaces.
The Woodward change notice gives coder compatibility 4.06 through 5.04, describes the model as non-preferred and lists planned inactivation in 2028. Confirm the installed footprint, RTN pairing, support status and backup requirements with Woodward.
5466-1035 — Non-preferred; Woodward's planned 2028 inactivation date is approximate and subject to change.
Non-preferred Woodward MicroNet CPU5200. Preserve the GAP application, tunables, firmware/coder footprint, RTN pairing and chassis configuration. The published planned 2028 inactivation date is approximate and subject to change.