Registered Address: 32D Floor Guomao Building, No.388, Hubin South Road, Siming District, Xiamen,Fujian, China
The ABB 200-CIE provides one 10 Mbit/s Ethernet channel for an Advant Controller 250 station. It uses CSMA/CD access and an AUI interface through a 15-pin female D connector, with power supplied from the controller backplane and an external 24 V DC source for the transceiver. A lithium battery supports retained data during controller power loss.
Selection is based on model 200-CIE, article 492897701, controller rack and AUI transceiver configuration.
Important Notice: Confirm the complete model, revision and installed system before replacement.
The module provides one 10 Mbit/s CSMA/CD channel through a 15-pin female AUI connector. The external medium attachment unit and cable must match the installed network segment.
Power is supplied from the controller system and a documented external 24 V DC source for the interface load. A 3.67 V, 0.8 Ah lithium battery supports retained information.
Verify article 492897701, backplane key 8, AUI transceiver, external supply, controller firmware and saved network settings before returning the station to service.
Engineering check: Connect 200-CIE through its 15-pin female D connector, AUI and verify a 10 Mbit/s CSMA/CD segment, transceiver power and shield bonding. Check that the attached AUI device stays within the 0.5 A maximum limit.
Acceptance test: Measure or replace the Lithium, 3.67 V, 0.8 Ah battery according to the maintenance procedure, preserve interface parameters, then interrupt and restore the Ethernet link while confirming address retention, link recovery and controller diagnostics.
Moore Automated supplies high-quality ABB 200-CIE replacement modules and Advant Controller spares. Exact article, rack compatibility and network interface are checked before supply to reduce commissioning risk and plant downtime.