Registered Address: 32D Floor Guomao Building, No.388, Hubin South Road, Siming District, Xiamen,Fujian, China
HE693SNP232A is a SNP-to-RS-232 adapter for a compatible GE Series 90-30 PLC programmer port. Its 15-pin connector interfaces with the SNP/RS-422 programmer port and provides a 9-pin RS-232 connection for a programming device. The adapter is powered by the PLC port and draws up to 100 mA at 5 V DC. Confirm connector pinout, CTS/RTS handshaking, cable wiring and serial settings before testing communications.
Signal conversion
Cable matching
The documented 9-pin RS-232 pinout permits a straight-through 1:1 connection to a compatible PC serial port. Confirm whether the connected device uses hardware handshaking before selecting the cable.
Check connector gender, TXD/RXD direction, CTS/RTS requirements and shield/ground practice against the receiving device documentation.
Communication checks
Confirm that the PLC-side port is the 15-pin SNP programmer interface and that the connected device uses the required 9-pin RS-232 pinout. Verify baud rate, parity and cable wiring before communication tests.
Product lifecycle: Not confirmed in available Horner Automation OEM materials; the legacy documentation identifies the adapter but does not state its lifecycle status.