489-P5-HI-A20 is a GE Multilin 489 generator protection and management relay.
489-P5-HI-A20 must be matched to the receiving equipment and project record. Perform secondary injection, trip-circuit, analog-output, communications and protection-setting verification before returning the generator to service.
Match the P5 current inputs and HI control-power range to the installed protection panel.
Transfer only the approved generator-protection settings and documented CT ratios.
Complete injection, trip, analog-output and communications tests before energizing the machine.
P5 specifies 5 A phase CT secondaries, HI specifies the high-range power supply, and A20 specifies 4–20 mA analog outputs. These options must match panel wiring and the saved relay file.
Verify CT polarity and ratios, trip circuits, control power, analog loops and every enabled protection element through an approved secondary-injection test.
Availability and lifecycle status are confirmed for the exact 489-P5-HI-A20 at quotation.