Registered Address: 32D Floor Guomao Building, No.388, Hubin South Road, Siming District, Xiamen,Fujian, China

Honeywell identifies DC-TCF901 as the Control Firewall input/output termination assembly for Series C Mark II. It connects the separate Control Firewall module and FTE cables and mounts on the Mark II cabinet backplane. The nine-port horizontal IOTA is a different model, CC-HCN911. Confirm extra site number 51307593-176 against the physical label.
Honeywell's April 2018 Control Firewall User's Guide identifies several distinct components in one table. CC-PCF901 is the active Control Firewall module. CC-TCF901 is a CF9 IOTA mounted on a carrier in a Series C cabinet. DC-TCF901 is the corresponding CF9 IOTA for Series C Mark II, mounted on that cabinet's backplane. CC-HCN911 is separately described as a horizontal nine-port FTE Control Firewall IOTA. These part distinctions are operationally important: a Mark II backplane IOTA should not be selected from a generic nine-port description or substituted for the active firewall module.
The DC-TCF901 description in the guide supports a physical connection role between the Control Firewall module and FTE cables. It does not assign independent firewall processing, a temperature rating, a port count or electrical performance limits to this exact assembly on the reviewed page. Capture the installed cabinet generation, backplane position, module marking, mating connectors, FTE cable assignments and existing diagnostics before an authorized change. Restore wiring and prove the affected network paths under site procedures. The Honeywell-authored document is mirrored outside the manufacturer domain and dated April 2018, so check current release applicability. The additional website number 51307593-176 is not mapped in the cited guide and must be verified from a physical label or manufacturer parts record.
DC-TCF901 is the CF9 termination assembly for Series C Mark II. The manufacturer table says it mounts on the Mark II backplane and physically connects the Control Firewall module and FTE cables. CC-PCF901 is the active module, while CC-HCN911 is the distinct horizontal nine-port IOTA. Confirm these printed model identities and the cabinet generation before interpreting any network or port claim for a replacement assembly.
The reviewed Honeywell guide distinguishes the carrier-mounted CC-TCF901 used in a Series C cabinet from backplane-mounted DC-TCF901 used in Series C Mark II. A similar product name does not establish mechanical interchangeability. Check the actual cabinet backplane, mating module, available mounting position, cabling and system release. The manufacturer excerpt does not validate a DC-TCF901 temperature rating, so use an applicable engineering specification rather than an inherited website value.
The cited PDF is a Honeywell-authored April 2018 guide hosted by a third-party mirror. Its component table explicitly names DC-TCF901, making the model role traceable, but it does not map extra website number 51307593-176. Request a photograph of the supplied label or a current Honeywell parts record before accepting that additional number. Preserve an approved service procedure and prove the affected FTE paths after installation.
Verify the exact DC-TCF901 model on the supplied assembly and reconcile extra 51307593-176 with the physical label or Honeywell parts record. Match the Series C Mark II cabinet backplane, the separate CC-PCF901 Control Firewall module, FTE cable arrangement and installed hardware revision. Do not treat the CC-HCN911 nine-port IOTA or carrier-mounted CC-TCF901 as automatically interchangeable. The reviewed guide does not establish a temperature rating for this exact IOTA.
Record cabinet type, backplane position, FTE cable labels, mating module, diagnostics and baseline network connectivity before approved work. Follow plant isolation, electrostatic protection and current Honeywell maintenance procedures. After installation, confirm physical seating and cable routing, then test the affected firewall interfaces and FTE paths under an authorized acceptance plan. The cited Honeywell-authored PDF is dated April 2018 and mirrored by a third party; verify its applicability to the installed Experion release and obtain authoritative mapping for the additional website number.