MC-TDOR62 is a coated, sixteen-circuit Honeywell relay output termination with fixed screw terminals. Its silver-alloy contacts are individually jumper-selected as normally open or normally closed, with 240 V AC / 125 V DC load service specified for the compatible PDOX02 arrangement.
The Honeywell MC-TDOR62 field termination assembly provides sixteen electromechanical relay outputs with fixed screw terminals. It belongs to the PDOX02 sixteen-output architecture. Each output uses a silver-alloy contact, with the designated jumper selecting normally open or normally closed operation. The maximum voltage limit is 265 V AC RMS or 140 V DC, but the permitted current depends on the load voltage and load characteristics rather than on that voltage limit alone.
For resistive loads, Honeywell lists 2.5 A at 240 V AC, 2 A at 30 V DC and 0.5 A at 125 V DC per output. The specified minimum current is 100 mA, and the manufacturer requires derating for lower power factor. Each contact has a 51-ohm/0.022-microfarad snubber and an individual 3 A, 250 V slow-blow fuse. Check contact configuration and protection before replacing the coated 307.3 by 120.65 mm size-B board.
The 2.5 A rating applies to a 240 V AC resistive load; it is not a universal contact-current allowance at every voltage. Use the separate DC ratings and manufacturer power-factor derating. Loads below 100 mA are outside the stated suitability of these power contacts.
Each output jumper selects a normally open or normally closed SPST contact arrangement. Record the installed positions and intended process behavior before replacement. The contact form must agree with the cabinet drawings; it does not by itself define the control-system fail-safe strategy.
The documented contact snubber is 51 ohms in combination with 0.022 microfarad, and each output has a 3 A, 250 V slow-blow fuse. Review load behavior and the approved protection before energizing the replacement. A fuse change does not increase the contact rating.
Review the field load voltage, steady-state current and load type for each output. Apply the separate AC and DC ratings and the manufacturer power-factor derating rather than treating the 265 V limit as an operating recommendation. Keep the 100 mA minimum load requirement in view when evaluating low-current electronic receivers or indicator circuits.
Record all output jumper positions, fixed screw-terminal assignments and individual fuse locations before service. Confirm the supplied coated board and complete assembly marking match the installed design. After reconnection, check each permitted contact operation and field response using the site commissioning procedure; do not rely solely on the control-system output indication to establish that a relay contact is healthy.