Registered Address: 32D Floor Guomao Building, No.388, Hubin South Road, Siming District, Xiamen,Fujian, China
PM866AK02 3BSE081637R1 is an ABB redundant processor kit used with the documented Advant AC800M platform. Selection must match the complete product identity, hardware execution, connected assemblies and approved system configuration.
Before replacing PM866AK02 3BSE081637R1, compare the supplied nameplate, revision, connectors or terminals and installed position with the original equipment record. After installation, review diagnostics and complete the approved functional checks before service.
ABB PM866AK02 3BSE081637R1 documentation and reference links.
Important Notice: Every linked document must identify the listed model or its documented family. Confirm the complete order code, hardware revision and installed-system requirements before replacement.
The OEM package lists two PM866A CPUs, two TP830 baseplates, two TB807 terminators, a TK850 CEX-bus expansion cable, a TK851 RCU-Link cable and two backup batteries. Match the written supply scope to this list; separately ordered communication modules are not implied.
For redundant PM866A operation, use the documented optical ModuleBus arrangement: seven optical clusters, no electrical cluster and up to 84 I/O modules. The controller also supports up to 12 CEX-bus communication modules, with architecture and power limits checked together.
Two 10 Mbit/s Ethernet ports on each baseplate connect to the Control Network, for which ABB recommends a 100 Mbit/s switched backbone. Do not confuse backbone speed with port speed. The COM3 and COM4 serial-interface specifications apply only to nonredundant configurations.
Engineering check: Treat PM866AK02 3BSE081637R1 as a matched redundant kit. Confirm both CPUs use the same MPC866 processor, 133 MHz clock, not stated memory, firmware revision and project checksum before pairing them on the controller base.
Acceptance test: Allow the primary and backup CPUs to synchronize fully, then perform an authorized switchover. Verify task continuity, retained values, CEX-bus communication, event timestamps and the absence of unresolved redundancy diagnostics.