Registered Address: 32D Floor Guomao Building, No.388, Hubin South Road, Siming District, Xiamen,Fujian, China
A panel-mount 3300 XL Proximitor Sensor calibrated for a 5.0 m total 8 mm transducer-system length. It powers the probe, conditions the eddy-current signal and provides voltage proportional to probe-to-target gap; code 05 identifies the multiple-approval option.
Confirm the complete 330180-50-05 identity and compare system length, mounting option and approval option with the installed design before approving a replacement.
Probe lead and extension cable must add to exactly 5.0 m and both must belong to the 3300 XL 8 mm family. NSv, 5 mm, 11 mm and 9.0 m components use different calibrations.
Mount the Proximitor on an isolated panel, preserve shield and common wiring, connect the matched 5.0 m probe chain, set the mechanical gap and confirm output scale and alarm-channel polarity.
Confirm 330180-50-05, including 50 for 5.0 m panel mounting and 05 for approvals. Do not substitute DIN-mount code 51 or 9.0 m codes 90/91 without checking the complete probe-plus-extension length.
For quotation, provide quantity, the complete 330180-50-05 label, clear nameplate and connector photographs, connected equipment, receiving country and required delivery date. Include project, firmware or hardware-revision records where applicable so Moore Automated can match and quote the exact item.