Registered Address: 32D Floor Guomao Building, No.388, Hubin South Road, Siming District, Xiamen,Fujian, China

CC-TAID01 51306733-175 is a Honeywell Experion Series C nonredundant analog-input IOTA for sixteen differential channels. Honeywell associates it with CC-PAIH02 HART or CC-PAIX02 non-HART analog-input modules and identifies a nominal nine-inch IOTA size. The IOTA is field termination hardware; conversion, scanning and module current belong to the installed IOM and must not be presented as IOTA specifications.
CC-TAID01 is the nonredundant Series C IOTA for sixteen differential analog-input channels. Honeywell's model table and function matrix associate it with CC-PAIH02 for HART-capable input service and CC-PAIX02 for non-HART input service. The IOTA provides the installed field-termination and IOM interface; it does not perform analog-to-digital conversion, establish scan rate or supply the IOM's accuracy specification. Those values come from the selected electronic module and its configured channel mode.
Honeywell identifies the coated CC-TAID01 as a nominal nine-inch IOTA. That value is an installed termination-assembly length, not a verified packed dimension. Replacement requires the same nonredundant architecture, exact terminal assignment, field-power arrangement, grounding, cable routing and compatible electronic module. Record the complete 51306733-175 marking and every conductor before removal. The redundant CC-TAID11 is a different architecture and should not be treated as an automatic physical substitute.
Use CC-TAID01 only with the approved Series C analog-input electronic module and controller release. The reviewed matrix pairs it with CC-PAIH02 for HART service or CC-PAIX02 for non-HART service. Confirm the installed IOM, firmware, database and intended signal functions before ordering.
Record every channel, polarity, shield, common, field-power source and grounding point before disconnecting the IOTA. Preserve the sixteen-channel differential arrangement and approved cable routing. The nominal nine-inch value describes installed IOTA length and must not be used as a packed-carton dimension.
After replacement, inspect keying and terminal torque, then perform authorized loop checks through the paired electronic module. Verify low, mid and high signal values, engineering-unit scaling, alarms, HART communication where CC-PAIH02 is used, and channel quality before returning each loop to service.
The IOTA provides sixteen differential field terminations and the interface to the selected Series C analog-input IOM. Preserve channel numbering, polarity, shield and common practices, external field power, grounding and cabinet keying. Select CC-PAIH02 when the approved design requires HART or CC-PAIX02 for the documented non-HART path; do not infer IOM performance from the termination assembly alone.
Photograph and label every conductor before removal, compare the complete 51306733-175 marking and inspect the connector and keying. Reconnect only against the approved terminal drawing. With the paired IOM and control database restored, inject authorized values, verify scaling and alarm behavior, confirm HART access where applicable, and document each channel result before plant service resumes.