Registered Address: 32D Floor Guomao Building, No.388, Hubin South Road, Siming District, Xiamen,Fujian, China
PROFINET IO master communication interface kit. Links an AC 800M controller to a verified PROFINET IO network through the CEX-Bus. Supports 10/100 Mbit/s Ethernet, module redundancy, hot swap and RJ45 connection.
CI871AK01 serves as the documented PROFINET IO master interface for the confirmed AC 800M configuration.
Compare the CEX-Bus position, TP867 base, station names, device topology, IP settings and redundancy design.
Preserve the controller project and network plan, then verify interface status and device communication after installation.
Engineering check: Commission CI871AK01 as a IO master on PROFINET IO. Match the controller hardware configuration, station name, IP subnet, update interval and RJ45 port assignment before downloading the control project.
Acceptance test: Run cyclic I/O at the configured update rate over the 10/100 Mbit/s link, review diagnostics for dropped or stale data, and—where redundancy is configured—prove cable or interface switchover without unintended output changes.