Registered Address: 32D Floor Guomao Building, No.388, Hubin South Road, Siming District, Xiamen,Fujian, China
MC-TAOX12 is a Honeywell eight-circuit analog output termination assembly for the redundant PAOX03 arrangement. It uses compression terminals on a size-B board; this record retains the complete 51304335-175 assembly marking.
The MC-TAOX12 51304335-175 listing is an MC coated eight-circuit analog output field termination assembly for the PAOX03 processor architecture. Honeywell identifies TAOX12 as the size-B arrangement used for redundancy, with compression terminals and a phone-connector-style processor connection. The normal system output is 4-20 mA; the specified maximum resistive load is 750 ohms at 22 mA. These are ratings of the processor and termination combination, not independent output generation by the board.
For replacement planning, the documented board footprint is 307.3 mm long by 120.65 mm wide. Honeywell specifies output perturbation of 1 ms nominal and 4 ms maximum during a swap, and 30 ms nominal and 125 ms maximum during failover, with switching-hardware diagnostics once per minute. The MC version is identified as coated in the ordering table; the numeric 51304335-175 assembly suffix is retained from the existing catalog and is not independently decoded by that family table. Preserve the installed output loops and redundant processor paths during service.
The eight field circuits belong to the PAOX03 analog output system. TAOX12 supports the documented redundant arrangement and is not the compact TAOX02 layout. Check both processor paths, the installed FTA cables and every loop assignment before replacing or reconfiguring the board.
The published transfer figures distinguish a processor swap from failover: swap perturbation is 1 ms nominal and 4 ms maximum, while failover perturbation is 30 ms nominal and 125 ms maximum. Review the receiving device response and configured control strategy before relying on those limits.
Compression field terminals and the phone-style processor connector must match the installed wiring. Record polarity, shielding and cable destinations, and allow access around the size-B board. The numeric assembly marking must be compared directly with the supplied item rather than treated as a documented revision code.
TAOX12 is listed with the eight-output PAOX03 processor, whereas the TAOY family uses a different sixteen-output architecture. Trace the installed output paths before replacement and retain the single-loop assignments. The specified 4-20 mA normal range, 750-ohm load limit at 22 mA and four-millisecond settling figure apply to the compatible processor/FTA combination, not to an arbitrary processor connected to the board.
The manufacturer distinguishes a controlled swap from failover: their maximum output perturbation figures are four milliseconds and 125 milliseconds respectively. Check that the field receiver and process strategy tolerate the actual transition. Preserve the redundant cable destinations, compression-terminal wire labels and approved output state during service, then test the transfer functions required by the installed system.
MC-TAOX12 is documented in Honeywell IO03-500 for the installed TPS Process Manager I/O platform. This specification establishes the termination function and compatible hardware, but is not a current model-specific lifecycle notice; no Active or Discontinued designation is asserted without that notice.
Moore Automated can check supply options for the exact MC-TAOX12 51304335-175 record, including board condition, conformally coated construction and connector form. Any substitute or migration requires review of the installed processor, FTA cabling and field wiring; availability does not establish OEM support status.