MC-TDOY22 is a conformally coated Honeywell field termination assembly for 32 digital outputs at 24 V DC. It is paired with PDOY22 processors and uses compression terminals in the size-B board format.
MC-TDOY22 connects 32 digital output circuits to 24 V DC field wiring in Honeywell PM I/O installations. The manufacturer specifies the PDOY22 processor family for this termination type and lists support for the corresponding redundant arrangement. Compression terminals provide the field connection, and the MC prefix identifies conformal coating. The FTA is only one component of the output path; the processor, field power arrangement and connected load must all match the approved cabinet design.
This board should not be confused with the TDOY23 relay termination, which provides only 16 field circuits per assembly, or with the TDOY62 screw-terminal version. Its size-B footprint measures 307.3 mm by 120.65 mm. Before replacement, identify every affected load and the expected output state during maintenance. Do not copy current or switching ratings from another output FTA, and do not describe all 24 V DC devices as compatible without checking their electrical load and protection requirements.
The PDOY22/TDOY22 arrangement uses current-sinking NPN open-collector outputs over a 15-30 V DC load range. Observe all three limits: 0.5 A per output, 1.0 A per two outputs and 5 A across the 32-output assembly. Nominal voltage alone is not a sufficient load check.
The required processor family is PDOY22, with the documented single or redundant arrangement. Trace the installed FTA cables to the correct processor positions and preserve their identification. A redundant-capable termination must not be treated as proof that the configured system has an operational backup processor.
This version uses compression field terminals. The TDOY62 variant uses nonremovable screw terminals, while the relay version changes the field output arrangement. Review terminal access, wire preparation and existing harness routing before selecting a replacement; matching the first letters of the model is insufficient.
Size the field loads against 0.5 A per point, 1.0 A per pair and 5 A total across 32 outputs. The TDOY22 arrangement uses one load fuse per two points, specified as 1.6 A, 125 V, 5.5 x 17.2 mm. These pair limits differ from the screw-terminal TDOY62 grouping. Confirm field supply polarity, current-sinking load wiring and the approved protective devices before energization.
Verify the full MC-TDOY22 marking, coating requirement, connector seating and PDOY22 processor pairing. Restore field connections to their original assignments and test outputs under the site commissioning plan. Confirm both the control-system indication and the actual field response where permitted; a healthy processor diagnostic alone does not prove the condition of the downstream wiring or load.