Registered Address: 32D Floor Guomao Building, No.388, Hubin South Road, Siming District, Xiamen,Fujian, China
MC-TDID72 is the coated, packaged Honeywell PM I/O field termination assembly for 32 digital inputs at 24 V DC. It uses removable screw terminals and is identified in the ordering table as the packaged version without plug-in isolators.
Honeywell MC-TDID72 is a packaged field termination assembly for 32 digital input circuits with 24 V DC field service. Its removable screw terminals provide a different maintenance interface from the compression and nonremovable-screw versions in the same broad termination family. The manufacturer ordering table explicitly identifies this packaged form as being without plug-in isolators. Accordingly, isolation or hazardous-area suitability must not be claimed merely from the packaged construction or the presence of conformal coating.
The manufacturer compatibility table associates TDID72 with the PDIX02 digital-input and PDIS12 sequence-of-events processor families. The size-C assembly uses a 462.28 mm by 120.65 mm board footprint. During replacement, preserve each removable connector location and field wire assignment, and verify the complete assembly marking. Processor selection and configured event functions remain separate from the termination board; the hardware should not be described as a standalone event recorder, safety input or universal digital interface.
The removable screw-terminal arrangement allows field connections to remain grouped, but each plug must return to its documented position and orientation. Record the connector labels and input assignments before service. Do not assume physically similar plugs from another FTA carry the same circuit assignments.
The packaged TDID72 uses optical isolation without removable plug-in isolators. Its documented field-to-system rating is 1500 V AC RMS or +/-1500 V DC, but that rating is not applicable when system power is used for the field inputs. Confirm the actual field-power arrangement before citing isolation.
The field board is listed with PDIX02 and PDIS12 processor families. Ordinary input status and sequence-of-events behavior depend on which processor and project configuration are installed. Verify the required input response and recording function through the system documentation before accepting a replacement.
For the documented 18-30 V DC range, ON sense current is at least 12 mA and OFF sense current is at most 4.3 mA. Guaranteed ON field resistance is no more than 100 ohms; guaranteed OFF resistance is at least 45 kilohms, reduced to 37.4 kilohms when operation is limited to 18-25 V DC. Observe the manufacturer ripple limit and the exception to field-to-system isolation when field inputs use system power.
Before removing a packaged assembly, identify the removable terminal plugs, field source and processor cable. Use the site isolation procedure, retain circuit labels and inspect connectors for damaged contacts or loose conductors. After reassembly, check representative and critical input states against the equipment indications and the configured database rather than relying only on a board-level status check.
MC-TDID72 is documented in Honeywell IO03-684 for the installed TPS Process Manager I/O platform. This specification establishes the termination function and compatible hardware, but is not a current model-specific lifecycle notice; no Active or Discontinued designation is asserted without that notice.
Moore Automated can check supply options for the exact MC-TDID72 51303928-150 record, including board condition, conformally coated construction and connector form. Any substitute or migration requires review of the installed processor, FTA cabling and field wiring; availability does not establish OEM support status.