- Analogue Input Module has eight isolated analogue input channels
- Belonging to the AADvance Controller platform
- Designed specifically for Safety Instrumented Systems (SIS)
The T9431 analogue input has eight isolated analogue input channels and measures input current in the range 0 mA to 24 mA. Each channel supplies digital state and analogue data to the processor for process monitoring.
The input module makes local module and channel status indications through its front panel LEDs, the same indications can be connected to application variables and viewed at the Workbench. Comprehensive diagnostics at system and module levels give clear indications which help fast maintenance and repair.
The T9431 ICS triplex Analogue Input Module may still be available for purchase and support from Moore Automated Company beyond End-Of-Life (EOL) by the manufacturer (OEM).
ICS Triplex T9431 Analogue Input Module maunal(Datasheets), Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Analogue Input Line Monitoring
Each analogue input module is set up through the AADvance Workbench. Monitoring levels for each input channel are configurable at both the module and channel level. The default parameters are:
Fault: 0 mA to 3.8 mA
Normal: 3.8 mA to 22.0 mA
Fault: > 22.0 mA
This module supports HART commands #03 to collect data from the field device. The application can be configured to use HART information to monitor and respond to device conditions, it may also be used to supply module diagnostic information such as comparison and error reporting.