Overview
Manuals
Configuration & Architecture
Certification Info
Features:
- 16 independently configurable channels supporting
- A/D update of all 16 Channels in 100 msecs
- Accuracy is ±0.1 % of Full Scale Range where FSR = 25 mA or 6.25 VDC
The RAI02J Redundant Analog Input module processes up to 16 high-level, group isolated, analog input field signals. Each channel is independently configurable for either 4 to 20 mA or 1 to +5 VDC ranges. FC 221 (I/O Device Definition) sets AI module operating parameters and each input channel is configured using FC 222 (Analog Input Channel) to set individual input channel parameters such as engineering units, High/Low alarm limits, etc.
A/D resolution of each channel is configurable from 12 to 16 bits with polarity. The RAI02J module has one A/D converter for all 16 input channels. The module will update 16 input channels in 100 msecs. In current mode, the RAI02J module supports HART v5.4 instruments and provides short circuit protection by limiting current to a maximum of 96 mA. The RAI02J module will also detect an open circuit in less than 5 seconds.
The RAI02J ABB Redundant Analog Input module may still be available for purchase and support from Moore Automated Company beyond End-Of-Life (EOL) by the manufacturer (OEM).
ABB RAI02J Redundant Analog Input module MANUAL(Datasheets), Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
This module operates within the ABB Symphony Plus/Symphony Enterprise system architecture. It utilizes function code (FC 221) for comprehensive device definition and parameter management, while the behavior of individual channels (such as engineering units and alarms) is handled by FC 223.
ESD immunity: Tested according to IEC/EN 61000-6-2, IEC/EN 61000-4-2, Severity level 3
Surge immunity: Tested according to IEC/EN 61000-6-2, IEC/EN 61000-4-5, Severity level 3
Electrical fast transient immunity: Tested according to IEC/EN 61000-6-2, IEC/EN 61000-4-4, Severity level 3
Radiated RFI immunity: Tested according to IEC/EN 61000-6-2, IEC/EN 61000-4-3, Severity level 3
Conducted Immunity: Tested according to IEC/EN 61000-6-2, IEC/EN 61000-4-6, Severity level 3
Magnetic field immunity: Tested according to IEC/EN 61000-6-2, IEC/EN 61000-4-8, Severity level 4
Radiated emission: Tested according to IEC/EN 61000-6-4, CISPR 11 + A1, CISPR 16-1-1, Group 1, Class A, ISM equipmentording to IEC/EN 61000-6-2, IEC/EN 61000-4-6, Severity level 3
Conducted emission: Tested according to IEC/EN 61000-6-4, CISPR 11 + A1, CISPR 16-1-1, Group 1, Class A, ISM equipment
Voltage dips and interruption immunity: Tested according to IEC/EN 61000-6-2, IEC/EN 61000-4-11