Overview
Manuals
Companion Slot Cable Types
Grounding & Safety Rules
Features:
- I/O Companion Slot, Internal, 40 Channel Input to FTA, 4.5m
- Trusted I/O Companion Slot Cables
- Certified to IEC 60332-3 Cat A standards
This type of Trusted I/O Companion Slot Cable is designed for use with analogue or digital input modules and is suitable for connecting input signals from an internal FTA to the module. The chassis end of the multi-core cable is fitted with two 96-way type ‘C’ connectors housed in a double-width hood.
The other end of the cable is fitted with a 96-way type ‘R’ connector housed in a single-width hood enabling the cable to be connected to an FTA. The multi-core cable is stripped back 1.5 m at both ends, then shrouded in nylon Rilgain sheathing. The ends of the sheathing are heated or fitted with over sleeving to help prevent fraying.
The TC-201-02-4M5 ICS Triplex Internal I/O Cable may still be available for purchase and support from Moore Automated Company beyond End-Of-Life (EOL) by the manufacturer (OEM).
ICS Triplex TC-201-02-4M5 Internal I/O Cable Manuals(Datasheets), Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
TC-201-03-xmx: I/O Companion Slot, Internal, 40 Channel Input to FTA (UL)
TC-202-02-xmx: I/O Companion Slot, Internal, 40 Channel Input to Flying Lead / Free Wire
TC-202-03-xmx: I/O Companion Slot, Internal, 40 Channel Input to Flying Lead / Free Wire (UL)
TC-203-02-xmx: I/O Companion Slot, External, 40 Channel Input to FTA
TC-203-03-xmx: I/O Companion Slot, External, 40 Channel Input to FTA (UL)
TC-204-02-xmx: I/O Companion Slot, External, 40 Channel Input to Flying Lead / Free Wire
TC-204-03-xmx: I/O Companion Slot, External, 40 Channel Input to Flying Lead / Free Wire (UL)
TC-205-02-xmx: I/O Companion Slot, Internal, 40 Channel Output to FTA
TC-205-03-xmx: I/O Companion Slot, Internal, 40 Channel Output to FTA (UL)
TC-206-02-xmx: I/O Companion Slot, Internal, 40 Channel Output to Flying Lead / Free Wire
TC-206-03-xmx: I/O Companion Slot, Internal, 40 Channel Output to Flying Lead / Free Wire(UL)
Chassis Grounding Integrity: Both ends of the chassis and the target FTA panel are equipped with dedicated built-in braided sheaths, allowing direct connection of the heavy-duty metal connector housing to the system safety ground bus.
Shielded Drain Isolation: At the far end, the multi-core internal shielded drain wire is clearly separated into a single green conductor. This conductor must be strictly connected to the instrument's shielded grounding node to reduce common-mode electromagnetic noise.